NGC Announces A New Power Transformer Tender

North Gas Company invites to bid for a new outdoor power transformer with the following specifications:

Rating 2000KVA

Cooling: ONAN

No-Load ratio : (3.3 /0.4) KV

Phases: 3

Frequency : 50HZ

No-load tap changer: 2*2.5%

Insulation Liquid : Oil

Vector Group: Dyn 11

Primary Connection: Delta

Secondary Connection: Star-Neutral

Ambient Conditions: Tropical/55 celsius degree

Neutral C.T Ratio (1000/5)

For further information , please click on this link.